Easy Topog-E Boiler Installation Instructions

1. Remove old gasket and thoroughly clean the surface on boiler and on cover plate. Sometimes it is necessary to buff each surface.

2. install1.jpg - 4.6 KPlace Topog-E Gasket on hanhole cover plate. Be sure the gasket is pushed down tight on the plate. Do not use any grease, lubricant, or adhesive.

3. install2.jpg - 5.0 KAfter cover plate is in boiler and gasket is in place, make one last cleaning swipe of the mating surface in the boiler. Use a rag wrapped around your finger.

blank.gif - 0.8 K
4. install3.jpg - 5.1 KSet crab, then center plate in opening and tighten nut enough to give a snug fit. Then, snug up with 1/4 turn of wrench.

SPECIAL NOTES:

Topog-E Bolt Gaskets (when required) should be used with Topog-E Handhole Gaskets.

Topog-E Gaskets are sold for use in steam, water, air, and other selected applications only. Recommendations for use of Topog-E Gaskets are based on tests believed to be reliable and on actual customer experience. Since their installation and use is beyond our control we cannot guarantee the results, whether or not such use is in accordance with directions. We disclaim any responsibility.